|

Tech Power Group
137 Home Ave
Darlington, SC 29532
Ph.336-214-2843
Fax.202-658-7448
Eastern Time Zone 
Login Status
|
|
Not logged in
|
| » Login |
|
|
| |
 |
 |
 |
Choosing the right Power UPS
Guide to professional UPS selection
|
The
following steps will guide you through the process
of specifying and selecting a
professional UPS for your organization. For a
newcomer to the UPS field it is advised to start
with
UPS Basics
article.
1.
Decide the required UPS Size.
The
Power Capacity of the required UPS should be the
first thing to decide. Connect to the
UPS only consumers which should be protected. The
UPS must back up servers,
Communication items, preferably Personal Computers,
and Emergency lights. Connect
monitors only if you need to provide service even if
power fails. Avoid connecting printers,
copiers, non-critical lights etc, even if the UPS
size permits.
Now calculate the total current drawn from the UPS,
which is the total sum of the currents of
every consumer connected to it. Multiplying thus
derived total current figure, by the local grid
Phase to Neutral voltage, (normally 120V in North
America or 230V in Europe) provides the
required VA Rating. Note the total current of a
three-phase system is derived by the sum of
all three phases.
The current demand of the consumers can be found in
the users manual or read from the
label attached to the instrument. To get the final
figure, reserve extra capacity for any
expected additional future Loads. The VA figure so
derived is in most cases 30% to 50 %
above the current, which the equipment consumes. You
will have to consult the manufacturer
of the equipment or measure the current for a more
accurate figure.
The wattage rating is the second figure to consider.
It represents the amount of real Power that
the load requires. The Watts to VA ratio, called
Power Factor, is dictated only by the nature of
the load. This ratio can theoretically be any number
between zero to one, but it is normally
between 0.6 to 0.8. Unless you have the exact
figure,Power Factor 0.7 should be OK for
Personal computers and 0.8 for large systems.
A personal computer (or server) including a monitor
will normally require no more than 300
VA. Multiplying the VA rating by a power factor of
0.7 renders 210Watt. The common
presentation is 300VA/210W.Thus, any UPS with a VA
rating equal to or above 300VA and
Watt rating equal to or above 210W should be
sufficient for a single computer.
2.Decide the required Autonomy time (Back-up time)
Autonomy time is the time that batteries are able to
back-up operation and feed the load upon
failure of utility power. Load consumption and size
of UPS batteries dictate the back-up time.
UPS systems rated below 20-30 KVA come normally with
internal batteries. Medium and high
power systems (above 3 to 5 KVA) are frequently
designed to allow back-up time expansion
by adding external batteries.
Statistically, the duration of 90% of utility power
outages is less than 5 minutes. The amount
of utility grid outages in the Western World is
about 10 to 30 per year. If you are not located in
a specific grid troublesome area, you may expect not
more than three power failures a year,
lasting beyond 5 minutes.
The main reason to purchase a UPS is to protect data
and hardware. Main causes of data
failures happen due to short time phenomena on the
utility grid, such as spikes, sags, dips, and
high frequency noise. Uncontrolled, abrupt power
failure can harm both software and
hardware. Data in process or not stored on the Hard
Disk is totally lost. In some cases, the
Hard Disk may also be entirely destroyed. The harm
done to it, if power fails during the writing
period for instance, is like a scratch made by the
needle of a phonograph record should you
turn it off while it is playing.
Unless you provide real time service, or your
equipment comprises part of a working industrial
process, which can't be interrupted, you might be
happy with a system that backs up your loads
for 5 minutes, and then turns off your computer in a
graceful manner. In most cases, mains
outage is shorter than 5 minutes, and UPS turn off
won’t be needed.
Therefore, 7-to 15 minute's back-up time should
suffice for most applications. You should
however make sure that the UPS is supplied with a
software suitable for your computer or
network, and that the software exits the system,
while storing on computers hard disk all open
files before turning down the computers, the way you
would do it manually.
You should also take in account that back up time is
strongly related to the size of your load.
UPS systems sense the battery voltage, emitting
audible alarm, including load turn off signal to
the computer, to allow orderly shut down, short time
before the battery discharges below a
preset voltage level, at which the UPS will turn
off. Lower load draws less current from the
batteries, extending the battery time.
APC's type LS 500 UPS for instance with 3.6 minutes
backup time at full load, provides 14
minutes back-up time at half load. Thus, over sizing
the UPS by 20 to 30%, which good
practice requires doing anyway, will enable you to
protect your computer network without
purchasing a system with bigger battery.
In applications which require continuous operation,
even during power absence, other and
additional factors should be considered. The battery
should be sized according to the required
autonomy time. The size of the UPS may have to be
increased because small units do not
allow battery extensions. You may need to increase
UPS size also in order to supply the
charging current of an extended external battery, or
in order to decrease the charging time
required by big battery bank. You might also
consider installation of a backup generator, to
feed the UPS. Cost, availability of space, and
reliability, should all be taken in consideration.
3.
Decide the type of the UPS you need
UPS's are roughly divided to three main classes. The
Off Line UPS is the simplest and the least
expensive, then comes the Line Interactive type,
which overcomes the major disadvantages
inherent to the off-line unit, finally the Double
Conversion On-Line UPS which provides the best
power protection.
An
off-line UPS,
also called
Stand-by
or Back-UP, feeds the load continuously from Mains.
Upon mains outage, the load connections transferred
to the inverter fed from the batteries.
Most of the short term spikes surges and high
frequency harmonics are decayed by means of
special filters. However, various phenomena of
transient nature during mains existence, like
over voltages and deeps can harm protected data.
These units are generally equipped with
spike suppressors, aimed to protect the hardware
from high voltages on the utility grid.
Off-line systems are used mainly for low power
installations, small offices, personal home
computers and other less critical application, where
eliminating 85% to 90% of computer
malfunctions caused by power failure, is
satisfactory. In such applications, this low cost
solution, is a good value for your money, it
decreases tenfold the probability of a harm to data
and hardware from utility Grid. The inverter output
voltage in this class is usually non-
sinusoidal, frequently called semi-sinusoidal.
Personal computers will probably work nicely
with such waveform. You should however check with
your vendor before using other types
of loads.
Professional installations generally require better
protection, Here comes the
Line Interactive
UPS,
called sometimes
Interactive UPS,
or
On
Line Interactive UPS.
These systems are
also based on stand-by principle, working directly
from mains, switching to battery (via the
inverter) upon mains disappearance. Here however,
additional circuits filter and correct output
voltage, keeping it within allowed tolerance band,
thus providing conditioned power to the
critical load. This UPS will probably have a
sinusoidal type inverter, therefore, special
precautions as regards to type of load might not be
required.
Line Interactive UPS units come generally in the
range of 500 to 5000 watts, offering a popular
solution for servers, personal computers hubs and
other loads in this power range. These units
are used mainly for short backup times, sufficient
to provide an orderly shut down.
Like the Off-Line unit, also here the stand by
behavior, is in most cases the major drawback of
the Interactive UPS. Practically, UPS operation is
verified upon mains failure which is the most
critical moment.Upon mains disappearance, the load
is connected to the inverter and batteries.
Any dormant malfunction, such as loose internal
connection or weak batteries might be
revealed at the very moment when it is called to
action.
Neither off-line nor Interactive UPS systems are
able to correct frequency. The output
frequency of any stand-by unit is in normal
operation the same as the input utility grid. These
units should therefore be avoided on sites equipped
with small back-up generators, exhibiting
generally poor frequency regulation.
The Interactive UPS is a professional solution for
business application where the main concern
is to provide software protection from about 90% to
95% of utility grid disturbances. These
units may be utilized in relatively small networks,
comprising 10-12 computers. They are
applied in such locations as lawyer offices,
accountants, sales agencies, engineering offices
etc.
Some prefer to back up with Interactive UPS less
critical equipment in the company, such as
personal computers connected to LAN network, whereas
the severs are backed up by an
ON -LINE UPS.
An
On-Line UPS,
also called
Double Conversion
UPS, or
True On-Line
UPS, is the ultimate
solution for all applications from one, or two
kilowatts up to Megawatt sized consumers. Here,
the load is constantly fed from the Inverter,
providing conditioned, stabilized sinusoidal
voltage.
The utility line in these systems forms a backup
source in case of UPS malfunction. The
Transfer switch will automatically transfer the load
to mains in case of overload or UPS failure.
The On-Line unit comprises two converting stages.
The first stage converts the incoming ac
power to DC, thus creating a dc-buss, which is fed
either from mains or from storage battery.
A second stage converts the DC power back to
conditioned ac in order to feed the critical load.
Filters on the DC buss and fast regulating circuits
in the converters practically isolate the load
from any abnormal utility behavior.
In normal operation, load energy comes from mains,
via the Rectifier and the Inverter. Upon
mains outage the battery supplies the energy, which
the load requires (by the dc/ac Inverter).
Should the mains voltage return before the battery
was fully discharged, the Rectifier will feed
the load through the Inverter and start a battery
recharge regime to compensate for the lost
charge.
Otherwise, the UPS will turn off when battery
becomes fully discharged. The UPS will resume
automatically normal operation upon mains
restoration. Also here, the Rectifier will feed the
load via the Inverter, recharging the battery.
The Output voltage of an On-Line UPS is generally
stabilized within one percent tolerance.
Output frequency is locked to input if it is within
preset tolerance band, otherwise a free
running crystal controlled clock will dictate the
output.
The merits of Double Conversion ON -Line system make
it the preferred choice for business
and industrial applications. It is the best solution
in spite of the added system and electricity
costs.
-
It offers the best power protection, covering
all types of mains disturbances
-
There is no size limit. Standard ON-Line UPS's
are available to backup any
installation
-
With the right system, no practical limit exists
on the available back-up time.
-
Many systems allow power extension to satisfy
the needs of a growing enterprise
-
Units can be connected in redundant
configuration to increase reliability or in
parallel to
enhance output power.
-
In addition, this is the best choice,
considering such issues as modularity, ability
to
work from generator, input power factor
correction, hot swapping, maintenance, fault
clearing, supervising, and communicating.
4.
Estimate the required Reliability
You
can rely on the UPS to back-up your system and
protect it from most power grid
problems. You should however consider Reliability
issues if you provide real time service.
Unfortunately,though the calculations are very
simple, some basic mathematical knowledge
might be required, if you want to make the
calculations yourself.
Reliability and Availability are the basic functions
for measuring UPS non-failure probability.
You should be acquainted also with some additional
interrelated terms, which describe different
Reliability aspects.
MTBF (Mean Time Between Failures), represents the
average time (generally in hours)
between expected failures. The UPS manufacturer
should supply the MTBF Figure (Either by
means of UPS data sheet or when requested.).
Failure Rate (λ = Reciprocal of MTBF) represents the
average number of failures during a
particular interval.
Reliability
(R
(t) = e ^ (- λt))
is defined as the probability of no failure before
time t. For
comparison purposes "t" refers normally to one year
(8760 hours).
Suppose the MTBF of a UPS is 100,000 hours. The
Reliability figure becomes 0.9161
(e
^ (-8760/100,000).
We can therefore expect that during one year
interval 91.6% of the time
(totaling 334 days) the UPS will operate
satisfactory and feed the load with conditioned
power,
but during 8.4% of the time (totaling 31 days) the
UPS will be down. In case of ON-Line
system the load will be fed during the down time
from, the utility grid.
For high mission requirements, this Reliability
figure is generally unacceptable. An additional,
Redundant, UPS can be connected to work in parallel
with the first unit. Thus, normally both
units share the load. Should one unit fail the
second will continue to feed the load. As long as
one system works correctly, the load is supplied
with conditioned voltage.
Evaluating the proper formula shows that the
Reliability figure will increase to 0.993. Thus
99.3% of the time it will be fed from the UPS. And
only 0.7% of the time ( 2.5 days per
annum ) it will depend on the reliability of the
utility power. Adding additional redundant units
increases the Reliability to any desired value.
In practice however, no UPS is left incorrect during
31 days. Two Additional Figures are used
to describe the real situation:
MTTR – Mean Time To Repair, expresses in Hours, the
total time, which takes to restore the
UPS to normal operation, starting from the moment
of its failure until the service personnel
complete their work.
Availability = MTBF/(MTBF + MTTR), represents the
degree to which the system is
operational when required.
Assuming that the stand alone UPS in our example
will be repaired on average within 24 Hours
(MTTR=24), the Availability becomes 0.99976
(100000/(100000+24)).
Meaning that
99.976% of the time the unit will supply conditioned
power. The down time now decreases to
2.1 hours per annum. We can further proceed to
improve this figure by adding additional
redundant units.
Parallel connection of UPS systems is possible only
if units operate at the same frequency, have
same voltage are synchronized, and have an ability
to isolate a faulty UPS disconnecting it from
the common output buss.
5.
Refine the deal
At
these stage you should already know the KVA rating
of the UPS you intend to buy, the
type of the UPS (Standby/Line Interactive/On-Line)
The autonomy time needed, and the
configuration (Stand alone or Redundant).
Now you can contact a nearby dealer, or try choosing
UPS system by yourself or by selecting
a suitable unit on the Web.
Here are some tips to help you while concluding
your Power UPS deal:
-
Increase UPS capacity to allow for future
expansion.
-
Don't buy backup time that you don't need.
Longer autonomy time does not mean
better equipment.
-
In case of Online units make sure you can add
external batteries in future, and that you
can increase power by adding parallel units if
expected
-
If you do not see a clear advantage for your
application, don't pay more. Higher price
does not necessary mean a better or more
reliable unit.
-
Don't buy any extras if you are not sure that
they are needed for your application.
Most can be added in the future whenever
required.
-
Some manufacturers provide 6-figure guarantee to
cover damage to your Equipment,
the enormous sums are seldom meaningful, you
won’t generally be paid above the value
of your backed up hardware. The main items, such
as loss of data, or discontinuity of
service to your clients are in most cases not
covered
-
Make sure that the UPS comes with software which
shuts down gracefully and
automatically all backed up computers.
-
Make sure that the UPS includes surge protectors
on input and on its
communication lines.
-
Make sure that the UPS performs automatic
battery tests, warning whenever the
batteries should be replaced. Otherwise you will
discover that your computer goes down when the lights turn off. Don't be tempted to
buy manually initiated test. Nobody remembers to keep the routine.
-
Avoid falling into a trap of misleading terms.
Smart UPS should regulate output Semi-
sinusoidal output is not sinusoidal. On -Line
must be double conversion and be able to
regulate output frequency. Note that "Automatic
self-test " does not always mean
battery test as well
-
Backup time has no meaning if you don't consider
the amount of UPS loading. Partial
load increases dramatically the time the
battery backs-up the equipment.
-
Prefer hot swap-able Batteries. The batteries of
some systems are not accessible by the
operator and should be replaced by qualified
technician.
-
When purchasing the UPS, make sure that after
sales service is in good hands. Check
who provides the service, how fast is it, and
whether it is provided in your premises.
-
Check Guarantee. Duration, Where and When. It
is not uncommon to get several
years guarantee, 7 days per week at your
premises.
-
Check the make of the UPS you are going to buy.
Check that manufacturing company
is at least ten years in the UPS business.
Get recommendation if it is unknown.
6.
Purchase the UPS
The
previous steps, provide
general
information about the system you might need.
This
information however
does not serve as a substitute to a professional
consultation.
Unless you
have a professional consultation, we strongly
advise to
make sure with
the supplier that his equipment works properly with
your specific computers
and loads, and that you are covered against any
possible malfunctions due
to inadequacy of the offered UPS to your critical
hardware.
Numerous manufacturers are probably able to meet
your requirements. Most provide well
designed and reliable systems. The top producers
are:
APC- MGE UPS Systems, GE, Gammatronic, Powerware-
Eaton and Liebert- Emerson,
Email or Call Tech Power Group for a detailed
consultation
|

|
 |
 |
 |
 |
|
|
| |
home | about us |
e-mail
|
|
|
Sales Of:
NetBotz
ArcMail
|